DC Inverter U-match Series Cassette Type Unit 
28 
(7)  Slightly open the liquid valve and let some refrigerant go to the connection pipe 
to balance the pressure inside and outside of the connection pipe, so that air will 
not come into the connection pipe when removing the hose. Note that the gas 
and liquid valve can be opened fully only after the manifold valve assembly is 
removed. 
(8)  Place back the caps of the liquid valve, gas valve and also the service port. 
Hose with the valve pin
gauge manifold
Pressure gauge (Low-pressure)
Pressure gauge (Hi-pressure)
Switch (Low-pressure)
Switch (Hi-pressure)
Connection pipe (to indoor unit)
Liquid valve
Gas valve
Service port
Cap
Hose
Vacuum pump
Cap
Service pipe
Cap
Connection pipe
 
Notice: 
For large-size units, there are maintenance ports for liquid valve and gas valve. 
During evacuation, you may connect the two hoses of the branch valve assembly to 
the maintenance ports to speed up the evacuation.   
3.2.4.2 Leak Detection Methods 
The  following  leak  detection  methods  are  deemed  acceptable  for  systems 
containing flammable refrigerants. 
Electronic leak detectors shall be used to detect flammable refrigerants, but the 
sensitivity may not be adequate, or may need re-calibration. (Detection equipment 
shall be calibrated in a refrigerant-free area). 
Ensure that the detector is not a potential source of ignition and is suitable for 
the refrigerant used. Leak detection equipment shall be set at a percentage of the 
LFL of the refrigerant and shall be calibrated to the refrigerant employed and the 
appropriate percentage of gas (25 % maximum) is confirmed. 
Leak detection fluids are suitable for use with most refrigerants but the use of 
detergents containing chlorine shall be avoided as the chlorine may react with the