refrigerant and corrode the copper pipe-work. 
If a  leak  is  suspected,  all  naked flames  shall  be  removed/extinguished.  If a 
leakage of refrigerant is found which requires brazing, all of the refrigerant shall be 
recovered from the system, or isolated (by means of shut off valves) in a part of the 
system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged 
through the system both before and during the brazing process. 
3.2.5 Refrigerant Adding 
Before and during operation, use an appropriate refrigerant leak detector to monitor 
the  operation  area  and  make  sure  the  technicians  can  be  well  aware  of  any 
potential or actual leakage of inflammable gas. Make sure the leak detecting device 
is applicable to inflammable refrigerant. For example, it should be free of sparks, 
completely sealed and safe in nature. 
See the following table for the amount of additional refrigerant. 
Unnecessary 
Charge Pipe Length   
Additional Refrigerant 
Amount for Extra Pipe   
3.2.6 Installation of Drain Pipe 
(1)  It is not allowed to connect the condensate drain pipe into waste pipe or other 
pipelines which are likely to produce corrosive or peculiar smell to prevent the 
smell from entering indoors or corrupt the unit. 
(2)  It is not allowed to connect the condensate drain pipe into rain pipe to prevent 
rain water from pouring in and cause property loss or personal injury. 
(3)  Condensate drain pipe should be connected into special drain system for air 
conditioner.