GREE DC INVERTER HEAT PUMP CONDENSING UNIT SERVICE MANUAL
90
Removal of Compressor/Gas Liquid Separator
NOTE: Before removing the compressor/gas liquid separator, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work Instruction
10. Connect the
compressor
wires.
Connect the
compressor wires to the
wire terminals on the
top of compressor.
NOTE: When
connecting the wires,
be sure to match the
colors with the
corresponding wire
terminals.
Model: GUD24W2/D-D(U), GUD30W2/D-D(U), GUD36W2/D-D(U)
Removal of 4-Way Valve
NOTE: Before removing the 4-way valve, make sure refrigerant is fully discharged from the unit and power is cut off.
Step Picture Work Instruction
1. Take off the coil of the
4-way valve.
Carefully unscrew the
screws of
electromagnetic coil with
a screwdriver.
2. Break off the connection
pipes from the 4-way
valve.
Use a soldering gun to
loosen the 4 joints on the
4-way valve and then
remove the connection
pipes.
NOTE: When welding the
pipes, the 4-way valve
should be wrapped with
wet cloth for cooling. Do
not let the flame burn the
other components.