GREE DC INVERTER HEAT PUMP CONDENSING UNIT SERVICE MANUAL
95
Removal of Condenser
NOTE:Before removing the condenser, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work Instruction
3. Remove motor support.
When removing the motor
support, be careful to
protect the components.
4. Break off the connection
pipes
Heat up the welding points
of connection pipes through
gas welding until the pipes
break off.
NOTE: When welding the
pipes, do not let the flame
burn the other components.
The welding points of
condenser are steel and
copper welding points. Be
sure to maintain the welding
quality.