GREE U-Match 6 SERIES UNIT SERVICE MANUAL
113
Removal of condenser
Note: Before removing the condenser, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
6. Install the new condenser.
Secure the screws of
condenser and support.
Then fix them together on
the chassis.
Install the condenser by
referring to the positions of
entering and leaving pipes.
Weld the connection pipes.
Nitrogen welding: the
pressure of nitrogen is
0.5±0.1kgf/ c (relative
pressure). Note: When
welding the pipes, do not let
the flame burn the other
components.
7. Secure the electric box and
arrange the wires
according to the
requirement.
Put the electric box in place
and tighten up the screws of
electric box.
Arrange and secure the
wires as original.
8. Check and open the upper
and side panels.
Check whether each
component and connection
wire is well connected.
If everything is OK, place
back the upper, left and
right side panels.