GREE U-Match 6 SERIES UNIT SERVICE MANUAL
112
Removal of condenser
Note: Before removing the condenser, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work instruction
3. Remove motor support.
When removing the motor
support, be careful to
protect the components.
4. Remove the condenser.
Heat up the welding points
of connection pipes through
gas welding until the pipes
break off. Note: When
welding the pipes, do not let
the flame burn the other
components. The welding
points of condenser are
steel and copper welding
points. Be sure to maintain
the welding quality.
5. Take out the condenser.
Loosen the securing screws
of condenser support. Take
off the plate type heat
exchanger and the support
as a whole.