GREE U-Match 6 SERIES UNIT SERVICE MANUAL
204
2. Temperature/Pressure List of
Refrigerant
R32
Pressure Temperature
Pressure Temperature
Pressure Temperature
Kpa
Kpa
Kpa
100 -51.909 1250 14.153 2400 38.688
150 -43.635 1300 15.52 2450 39.529
200 -37.323 1350 16.847 2500 40.358
250 -32.15 1400 18.138 2550 41.173
300 -27.731 1450 19.395 2600 41.977
350 -23.85 1500 20.619 2650 42.769
400 -20.378 1550 21.813 2700 43.55
450 -17.225 1600 22.978 2750 44.32
500 -14.331 1650 24.116 2800 45.079
550 -11.65 1700 25.229 2850 45.828
600 -9.1503 1750 26.317 2900 46.567
650 -6.8046 1800 27.382 2950 47.296
700 -4.5925 1850 28.425 3000 48.015
750 -2.4975 1900 29.447 3050 48.726
800 -0.50613 1950 30.448 3100 49.428
850 1.393 2000 31.431 3150 50.121
900 3.2092 2050 32.395 3200 50.806
950 4.9506 2100 33.341 3250 51.482
1000 6.624 2150 34.271 3300 52.15
1050 8.2352 2200 35.184 3350 52.811
1100 9.7896 2250 36.082 3400 53.464
1150 11.291 2300 36.965 3450 54.11
1200 12.745 2350 37.834 3500 54.748
3. Refrigerant Notice/Concentration
This air conditioner uses R32 refrigerant. The construction area for installation, operation and storage
of the air conditioner must be larger than the minimum construction area. The minimum area for
installation is determined by:
1.Refrigerant charging quantity for the entire system (ex-factory charging quantity + additional
charging quantity);
2.Checking out in the applicable tables:
(1) For indoor unit, confirm the model of indoor unit and check the corresponding table.
(2) For outdoor unit that is installed or placed indoors, select the corresponding table according to
the height of the room.