77
U-MATCH Air
Conditioners
Service Manual
4.1.3 Power Cable Connection
1. Air-conditioning unit with single-phase power supply
Remove the front-side panel of the outdoor unit.
Pass the cable though rubber ring.
Connect the power supply cable to the “L, N” terminals and the grounding screw.
8VHFDEOHIDVWHQHUWREXQGOHDQG¿[WKHFDEOH
2. Air-conditioning unit with 3-phase power supply
Remove the front-side panel of the outdoor unit.
Attach rubber ring to the cable-cross hole of the outdoor unit.
Pass the cable though rubber ring.
Connect the power cable to the terminal and earthing screws marked “L1, L2, L3 & N”.
8VHFDEOHIDVWHQHUWREXQGOHDQG¿[WKHFDEOH
Caution: )RUDLUFRQGLWLRQHUZLWKDX[LOLDU\KHDWHULWLVUHTXLUHGWRFRQQHFWWKHSRZHUFDEOHWRWKH³//
L3”terminals and the grounding screw.
4.1.4 Connection of Signal Line of Wire Controller
Caution: Take great care when carrying out the following connections, so as to avoid malfunction of the air-
conditioning unit because of electromagnetic interference.
The signal line of the wire controller must be separated from the power line and the connecting line
between the indoor unit and the outdoor unit.
In case the unit is installed in a place vulnerable by electromagnetic interference, it is better to use shielded
cable or double-twisted cable as the signal line of the wire controller.
Open the cover of the electric box of the indoor unit.
Pull the signal cable of the wire controller through the rubber ring.
Plug the signal line of the wire controller onto the 4-bit pin socket at the circuit board of the indoor unit.
8VHFDEOHIDVWHQHUWREXQGOHDQG¿[WKHVLJQDOFDEOHRIWKHZLUHFRQWUROOHU
4.1.5 Connection of wires
Remove the board on the right side of outdoor unit and put through the wire running hole on the outdoor
unit and put on a rubber ring.
5HPRYHZLUHKROGHUVDQGFRQQHFWWKHSRZHUFRUGWRWKHWHUPLQDODQG¿[LW
Secure the power connecting cord and signal control cable with wire holders and then connect
corresponding adapters.
&KHFNLIZLUHVDUH¿[HGSURSHUO\
Fit on the front side board.
4.2 Electric Wiring Design
Duct Type
*8+11.$2*)+.%,*8+11.$2*)+.%,
*8+11.$2*)+.%,*8+11.$2*)+.%,
*8+11.$2*)+.%,*8+11.$2*)+.%,