EasyManua.ls Logo

Gree GWH09AB-A3DNA1B - Page 52

Gree GWH09AB-A3DNA1B
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2. Low voltage overcurrent protection
Possi ble reason: Sudden drop of supply voltage.
3. Communic ation malfun ction
Processin g method: Check if communic ation signal cable is c onnected reliably.
4. Senso r open or shor t circuit
Processin g meth od: Check whether s ensor is normal, c onnected with the corre sponding po sition on th e
controller and if damage of lead wire is found.
5. Compressor over load protection
Possi ble rea sons: insufficient or too much refrigrant; blockage of capillary an d increas e of suct ion temp.;
improp er running of compressor, burning in or stuck of bea ring, damage of discharge valve;
malfunc tion of pro tector.
Processi ng method: adjust refrige rant amount; replace the capillary; replace the compressor; use
univers al meter to check if the cont acto r of compress or is fine wh en it is not overh eated , if not replace
the prote ctor.
6. System malfun ction
i.e.overloadprotection.Whentubetemperature(Check thetemperatureof outdoor heat exchanger
when cooling and check the temperatur e of indoor heat exchanger when heating) is too high,
protectionwill beactivated.
Possi ble reasons: Outdoor tempera ture is too high when cooling; insufficient outdoor air circulation;
refrigerant flow malfunction.
please refer to the malfunction analysis in the previous section for handling method .
7. IPM module protection
Processing method:Once the module malfunction happens,if it persists for a long time and can not be self- canceled,
cut off the power and turn off the unit,and then re-energize the unit again after about 10 min.After repeating the
procedure for sever times, if the malfunction still exists,replace the module.
Analysis or processing of some of the malfunction display:
1. Compressor discharge protection
Possible reasons: shortage of refrigerant; blockage of air filter; poor ventilation or air flow short pass for condenser;
the system has noncondensing gas (such as air, water etc.); blockage of capillary assy (including filter); leakage
inside four-way valve causes incorrect operation; malfunction of compressor; malfunction of protection relay;
malfunction of discharge sensor; outdoor temperature too high.
Processing method: refer to the malfunction analysis in the above section.
Troubleshooting
49

Other manuals for Gree GWH09AB-A3DNA1B

Related product manuals