Service Manual
9.  Maintenance
9.1 Error Code List
NO.
Malfunction
Name
Display Method of Indoor Unit
Display Method of Outdoor 
Unit
A/C status Possible Causes
Dual-8
Code
Display
Indicator Display (during 
blinking,  ON 0.5s and OFF 
0.5s)
Indicator has 3 kinds of 
display status and during 
blinking,  ON 0.5s and OFF 
0.5s
Operation
Indicator
Cool
Indicator
Heating
Indicator
Yellow
Indicator
Red
Indicator
Green
Indicator
1
High 
pressure 
protection of 
system
E1
During cooling and drying 
operation, except indoor 
fan operates,  all loads stop 
operation.
During heating operation, the 
complete unit stops.
Possible reasons:
1.  Refrigerant was superabundant;
2.  Poor heat exchange (including 
filth blockage of heat exchanger 
and bad radiating environment ); 
Ambient temperature is too high.
2
Antifreezing
protection
E2
OFF  1S 
and blink 
3 times
During cooling and drying 
operation, compressor and 
outdoor fan stop while indoor 
fan operates.
1.  Poor air-return in indoor unit;
2.  Fan speed is abnormal;
3.  Evaporator is dirty.
3
Refrigerant
leakage
protection
F0
OFF  1S 
and 
blink 
9 times
The Dual-8 Code Display will 
show F0 and the complete unit 
stops.
1.Refrigerant leakage;
2.Indoor evaporator temperature 
sensor works abnormally; 
3.The unit has been plugged  up 
somewhere.
4
High
discharge 
temperature 
protection of 
compressor
E4
OFF  1S 
and blink 
7 times
During cooling and drying 
operation, compressor and 
outdoor fan stop while indoor 
fan operates.  During heating 
operation, all loads stop.
Please refer to the malfunction 
analysis (discharge protection, 
overload).
5
Overcurrent
protection
E5
OFF 1S 
and blink 
5 times
During cooling and drying 
operation, compressor and 
outdoor fan stop while indoor 
fan operates.  During heating 
operation, all loads stop.
1. Supply voltage is unstable;
2. Supply voltage is too low and 
load is too high;
3.  Evaporator is dirty.
6
Communi
cation
Malfunction
E6
Always
During cooling operation, 
compressor stops while 
indoor fan motor operates. 
During heating operation,  the 
complete unit stops.
Refer to the corresponding 
malfunction analysis.
7
High
temperature
resistant
protection
E8
OFF  1S 
and blink 
6 times
During cooling operation: 
compressor will stop while 
indoor fan will operate.
During heating operation,  the 
complete unit stops.
Refer to the malfunction analysis 
(overload,  high temperature 
resistant).
8
EEPROM
malfunction
EE
OFF  1S 
and blink 
11  times
During cooling and drying 
operation, compressor will stop 
while indoor fan will operate; 
During heating operation,  the 
complete unit will stop
Replace outdoor control panel AP1
9
Limit/ 
decrease 
frequency 
due to high 
temperature 
of module
EU
All loads operate normally, 
while
operation frequency for 
compressor is decreased
Discharging after the complete unit 
is de-energized for 20mins,  check 
whether the thermal grease on 
IPM Module of outdoor control 
panel AP1  is sufficient and whether 
the radiator is inserted tightly.
If its no use, please replace control 
panel AP1.
10
Malfunction 
protection of 
jumper cap
C5
Wireless remote receiver and 
button are effective, but can 
not dispose the related 
command
1. No jumper cap insert on 
mainboard.
2. Incorrect insert of jumper cap.
3. Jumper cap damaged.
4. Abnormal detecting circuit of 
mainboard.