Service Manual
2. IPM protection(H 5), de sy nc hro n iz in g m alfu n ction (H 7), ove rc urre nt o f co m pres so r phase cu rre n t (P5) (AP1 belo w m eans
co n tro l board o f ou td o o r unit)
Main detection points:
Is voltage input within the normal range
If the control board AP1 is well connected with compressor COMP? If they are loosened? If the connection sequence is correct?
Heat exchange of unit is not good (heat exchanger is dirty and unit radiating environment is bad);
If the system pressure is too high?
If the refrigerant charging amount is appropriate?
If coil resistance of compressor is normal? Is compressor coil insulating to copper pipe well?
If the work load of unit is heavy? If radiating of unit is good?
Malfunction diagnosis process: