EasyManua.ls Logo

Gree GWH36LB-K3NTA5A - Capacity Curve in Different Outdoor Temperature; Operation Data

Gree GWH36LB-K3NTA5A
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
7HFKQLFDO,QIRUPDWLRQ
Service Manual
2.2 Capacity Curve in Different Outdoor Temperature
Rated cooling condition(°C)
(DB/WB)
Model
Pressure of gas pipe
connecting indoor and
outdoor unit
Inlet and outlet pipe temperature
RIKHDWH[FKDQJHU
Fan speed of
indoor unit
Fan speed of
outdoor unit
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
27/19 35/24 36K 0.9 to 1.1 8~11 to 11~14 75~85 to 37~43 6XSHU+LJK +LJK
2.3 Operation Data
Cooling
Heating
5DWHGKHDWLQJFRQGLWLRQ&
(DB/WB)
Model
Pressure of gas pipe
connecting indoor and
outdoor unit
Inlet and outlet pipe temperature
RIKHDWH[FKDQJHU
Fan speed of
indoor unit
Fan speed of
outdoor unit
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
20/- 7/6 36K 2.8 to 3.0 85 to 35 2 to 4 6XSHU+LJK +LJK
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: .Inlet and outlet pipe temperature of condenser
33UHVVXUHDWWKHVLGHRIELJYDOYH
&RQQHFWLRQSLSHOHQJWKP
Cooling Heating
Capacity ratio(%)
110
100
90
80
70
60
50
51 53 55494745434139373533312927252321
1574220-7-10 -5
0
20
40
60
80
100
120
510
Capacity ratio(%)
Condition Cooling
Indoor:DB27°C WB19°C
Indoor air flow: Super High
Pipe length:5m
Condition Heating
Indoor:DB20°C
Indoor air flow: Super High
Pipe length:5m
Outdoor temp.(°C)
Outdoor temp.(°C)