GREE Air-ccoled Closed Control Unit Service Manual
46
.”: Decimal point, which for its input.
ES”: By touching to cancel the input and the keyboard will disappear.
CR”: By touching to erase the number inputted previously to input afresh.
ENT”: By touching to confirm the input and the keyboard will disappear which means
finishing of the input.
There are “max” value and “min” value on the top of the keyboard that are corresponding to
the input range in the numeric box. If the numeric value exceeded the range is inputted, this
input is invalid.
When the touch screen is shielded, “
Shield Touch Screen! Invalid Setting!” will be
shown on the right side of the interface. In that case, each setting interface is read-only and its
parameter setting cannot be revised.
2Module Mode Setting
Slightly press the button “Module Setting” to enter the interface of “Module Mode Setting”
Only when unit is set off on the homepage can the mode setting of each module be
effective on this interface.
Link/Break”: When the connection is set, the module is connecting with and controlled
by the main module; When the disconnection is set, the communication breaks and the module
is out of control. At that time, related units are auto turned off which will be turned on by setting
connection and the data of the unit on the touch screen shows 0.
ON/OFF”: It means the unit of the module in the ON/OFF state.
Entire/ Alone”: When the entire running is set, the module will be running together with
the other entire modules, including alternate running, standby running; When the Alone running
is set, the module will be running alone. Temp. and humidity is Subject to the unit itself without
functions of alternation and standby.