GREE Air-ccoled Closed Control Unit Service Manual
45
Max value of return air humidity setting=upper limit setting of return air humidity - 3 , ℃
minimum value of return air humidity setting=lower limit setting of return air humidity+ 3 ,℃
Minimum value of upper limit setting of return air temperature(alarm) >=integer of return air
temperature setting + 2 ,
℃
Maximum value of lower limit setting of return air humidity(alarm)=integer of return air
temperature setting - 2 .
℃
“
Module Mode Setting”、“Time Setting”、“Timer Setting.”:Slightly press these buttons
to enter the corresponding setting page.
“Numeric Value Input”: The numeric value with box represents what can be revised. By
touching the number in the box, the keyboard interface is popped up and the number in the
touched box displays the blinking cursor which means the number in the input state.
Touch the number in the keyboard. Input the revised number, and finally touch the “ENT”
button in the keyboard to confirm the input. The keyboard will disappear subsequently, which
means the finishing of the input.
Introduction to the buttons on keyboard:
“
Number Key”: Number 0~9.