Receiver JS13
4
3.1.1 Selection Requirement for Communication Wire
Figure 3-2 Length of Communication Wire
Wire material type
Total length of
communication
wire between
indoor unit and
wired controller L
(m)
Wire size
(mm
2
)
Material
standard
Remarks
Light/Ordinary
polyvinyl chloride
sheathed twisted
pair cord
L≤250
2×0.75~
2×1.25
GB/T 5023.5-
2008
Total length of
communication wire
can't exceed 250m.
Shielded
light/Ordinary
polyvinyl chloride
sheathed twisted
pair cord
L≤250
2×0.75~
2×1.25
GB/T 5023.5-
2008
If unit is installed in
places with intense
magnetic field or strong
interference, it is
necessary to use
shielded wire
NOTES:
If unit is installed in places with intense magnetic field or strong interference,
the communication wire of the receiver must be shielded twisted wire.