S2S KNX Gateway
28
Object# 26
Name Object for disable – Disable
Function Control/feed back the ON/OFF of forbidden object
Description 0: OFF, 1: ON
Read/Write Write/Read
Type of data point 1 bit
Object# 27
Name Scene recall or save – Scene
Function Activate/learn the corresponding scene
Description
Send one 8-bit command through this communication
object can invoke or save the scene of air conditioner.
The following will explain the meaning of 8-bit
command in detail.
Set one 8bit command as (binary coding):
FXNNNNNN
F: when it is ‘0’, invoke the scene; when it is ‘1’, save
the scene;
X:0;
NNNNNN: scene number (0…63)
Parameter setting option is 1~64, actually, the
corresponding scene message received by
communication object “Scene” is 0~63. If the
parameter set the scene is 1, the scene received by
communication object “Scene” is 0.
Read/Write Write
Type of data point 1 byte