EasyManua.ls Logo

Greenheck DGX - Page 47

Greenheck DGX
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
47
Reference
Control Center Layout
Reference
1. Heating/Cooling Inlet Air Sensor (Optional) - Ductstat that automatically de-energizes burner when inlet air
temperature rises above set point, or shuts down cooling when temperature falls below set point.
2. Flame Safeguard/Spark Generator - Monitors flame, shuts down unit when unsafe conditions are detected.
3. High Limit - Prevents unit from discharging air above a set point.
4. Building Freeze Protection (Optional) - Prevents unit from discharging air below a set point after a time
delay. Temperature and time delay are field adjustable.
5. Filter Gauge (Optional) - Monitors filter pressure drop, turns on indicating light when pressure drop is
above field adjustable set point.
6. Terminal Strip - 24 Volt power strip for control wiring.
7. Main Disconnect - On/Off switch, provides single point power connection to unit.
8. Grounding Lugs - Completes electrical circuit
9. Motor Starters - 24 Volt magnetic contacts for starting motors, comes standard with electronic overload,
may be provided with auxiliary contacts.
10. Amplifier - Controls modulating valve, assures the desired temperature is delivered.
11. Low Voltage Transformer - Reduces voltage to the Maxitrol system.
12. Control Transformer - Provides 24 Volts for controls and 120 Volts for valves.
13. Secondary fuses - Provides proper fusing for all electrical components other than the motors.
14. Motor Fuses - Provides proper fusing for supply and exhaust fan motor(s).
Figure 67. Direct Spark Gas Control Center
1
2
10
3
4
6
11
13
14
9
7
8
12
5

Related product manuals