High Volume, Low Speed Ceiling Fans
®
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with these instructions will result in voiding of the product warranty and may result in personal injury
and/or property damage.
1
Document 483568
Model DS
High Volume, Low Speed Ceiling Fans
Models DS-3 and DS-6 are the ideal choice for providing year-round comfort in air circulation and destratification
applications. Featuring an aerodynamic, extruded aluminum airfoil design and a high efficiency direct drive motor,
model DS delivers maximum airflow at a fraction of the operating cost of other HVLS fans. And, with its universal
ceiling mount, the DS fan is the easiest HVLS fan to install in the market!
IMPORTANT: To reduce the risk of fire, electric shock,
or injury to persons, Model DS fans must be installed
with a mount assembly, motor assembly and airfoils that
are marked (on their cartons) to indicate suitability with
this model. Other mounts, motors, and airfoils cannot
be substituted.
WARNING
To reduce the risk of fire, electric shock, or injury to
persons, observe the following:
1. Use this unit only in the manner intended by the
manufacturer. If you have questions, contact the
manufacturer.
2. Before servicing or cleaning unit, switch
power off at service panel and lock the service
disconnecting means to prevent power from
being switched on accidentally. When the service
disconnecting means cannot be locked, securely
fasten a prominent warning device, such as a tag,
to the service panel.
WARNING
To reduce the risk of fire, electric shock, or injury to
persons, observe the following:
1. Installation work and electrical wiring must be
done by qualified person(s) in accordance with all
applicable codes and standards, including fire-
rated construction.
2. When cutting or drilling into wall or ceiling, do
not damage electrical wiring and other hidden
utilities.
WARNING
This appliance can be used by children aged from 8
years and above and persons with reduced physical,
sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or
instruction concerning use of the appliance in a safe
way and understand the hazards involved. Children
shall not play with the appliance. Cleaning and user
maintenance shall not be made by children without
supervision.
General Safety Information
IMPORTANT: DS fans must be installed with the supplied CAT-5e communication cable or shielded CAT-5e
(by others) that complies with the following specifications. Cable must be twisted pair, shielded 26 ga. CAT-5e
cable with a drain wire and must be compliant with ISO 11801. Cable must use shielded RJ45 connectors with
a soldered drain and wiring configuration must follow EIA/TIA T568B wiring pinout. Individual CAT-5e cable
lengths must not exceed 200 ft. in order to prevent network communication issues.

Questions and Answers:

Greenheck DS Specifications

General IconGeneral
BrandGreenheck
ModelDS
CategoryFan
LanguageEnglish

Summary

General Safety Information

Receiving

Unpacking

Storage

Inspection & Maintenance During Storage

Pre-Installation Checks

Minimum Spacing Requirements

Fan Components

Required Tools

Mounting Installation

I-Beam Mounting Kit

Instructions for mounting the fan to I-beams up to 10 inches wide.

Steel Truss Mounting Kit

Steps for installing the fan mount onto steel trusses or bar joists.

Wood Beam Mounting Kit

Z-Purlin Mounting Kit

Unistrut® Mounting Kit (By Others)

Motor/Hub to Downtube Installation

Fan Networking

Safety Retention Cable Installation

Gripple® Hardware (Optional)

Guy Wire Installation

Airfoil Blade & Winglet Installation

Hub Plate Installation

LED Light Installation (Optional)

Wiring and Electrical – Factory Wiring Installation

Fire Alarm Relay Installation

Instructions for installing the fire alarm relay for buildings with suppression systems.

Communication Wiring & Fan Control Installation

Guides for connecting the fan for control and networking via CAT-5e.

Communication Wiring (Bulk Spool)

Power Wiring Installation

Disconnect and Fuse Installation

Pre-Start-Up Checks

Operation

Inspection

Maintenance

Troubleshooting

Modbus Registers

Maintenance Log

Related product manuals