EasyManua.ls Logo

Greenheck Vektor Series - User Manual

Greenheck Vektor Series
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble,
install, operate or maintain the product described. Protect yourself and others by observing all safety
information. Failure to comply with instructions could result in personal injury and/or property damage!
1
VGN Technology
®
®
Document 481885
Vektor
®
Laboratory Exhaust
with Variable Geometry Nozzle (VGN) Technology
Electrical Controls Information
DANGER
Always disconnect power before working on or near a
unit. Lock and tag the disconnect switch or breaker to
prevent accidental power up.
CAUTION
When servicing the unit, variable frequency drives
(VFD) may be hot enough to cause pain or injury.
Allow motor to cool before servicing.
General Safety Information
Only qualified personnel should install this unit.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards. Other
considerations may be required if high winds or seismic
activity are present. If more information is needed,
contact a licensed professional engineer before moving
forward.
1. Follow all local electrical and safety codes, as well as
the National Electrical Code (NEC), the National Fire
Protection Agency (NFPA), where applicable. Follow
the Canadian Electrical Code (CEC) in Canada.
2. Do not allow the power cable to kink or come in
contact with oil, grease, hot surfaces, or chemicals.
Replace cord immediately if damaged.
3. Verify the power source is compatible with the
equipment.
Table of Contents
Receiving, Handling and Storage .................2
Variable Geometry Nozzle (VGN) Control System
Components ................................3
Quick Installation Guide .........................4
VGN System Function Overview
Mounting of VGN Controller ....................5
Nozzle to Pressure Transducer Box ..............5
VGN Controller to Pressure Transducer Box .......5
VGN Controller to VFD and BMS Hardwiring
Fan Run Signal ..............................6
BMS Communication .........................6
Nozzle Feedback ............................6
Fan Flow ..................................6
Outlet Velocity: On the Fly Unoccupied Adjustment 7
VGN Controller Incoming Power Wiring Instructions. . . 7
BMS Communication Programming
Fan Run Signal ..............................8
Nozzle Feedback ............................8
Fan Flow ...................................8
Alarm......................................8
Outlet Velocity: On the Fly Unoccupied Adjustment
and Example ............................8-9
Wiring Diagram - Single Fan and Multiple Fans . . 10-11
Start-Up Procedure
Mechanical Component System Verification ......12
Electrical Components System Verification .......12
System Start-Up Preparation for VGN ...........12
System Start-Up for VGN ..................12-13
Test and Balance for VGN ....................13
Calibrating Carel CFM Display with Test and
Balance Procedure ........................13
VGN Controller Introduction, Tutorial, Operator Interface
and Keypad Navigation ........................14
Status ....................................15
On/Off Unit ................................15
Set Points (Test and Balance)..................16
Clock/Scheduler ............................17
Inputs/Outputs ..........................17-18
Alarm History ..............................18
Technician .................................19
Factory ...................................20
Troubleshooting ..............................21
VGN Technology Maintenance...................22
VGN Technology Electrical Replacement Parts ......22
Maintenance Record ..........................23
Our Commitment ......................Backcover
Single Fan
VGN Controller
Multiple Fan
VGN Controller

Questions and Answers

  • H
    Henry SimmonsJul 27, 2025
    Why does my Greenheck Vektor Ventilation Hood system have positive pressure?
    • M
      Michael JohnsonJul 27, 2025
      A positive pressure condition in your Greenheck Ventilation Hood system can stem from several causes. First, check the power at the isolation damper to ensure it is open. Verify that the BMS control is functioning correctly, especially at full speed with the bypass closed. Inspect the duct pressure transducer(s) for proper power and signal. A broken fan belt or an open bypass damper can also lead to this issue, so inspect those components. Ensure all access panels on the fan or bypass air plenum are in place, and check the actuator power and signal to ensure the nozzle is operating correctly and not stuck at minimum area.
  • T
    Timothy TuckerJul 31, 2025
    What to do if CFM reading is low on Greenheck Vektor?
    • C
      Caitlin MartinJul 31, 2025
      If your Greenheck Ventilation Hood shows a low or zero CFM reading despite the fan operating, several factors could be responsible. Start by checking the power to the isolation damper to ensure it's open. Inspect the Sure-Aire tubing for leaks or blockages, and try blowing it out with air. Make sure the Sure-Aire tube lines are correctly hooked up, not backwards. Test the Sure-Aire transducer for the system to ensure it's receiving 24V and outputting a signal. Finally, ensure all laboratory hoods are open to verify proper operation.
  • J
    johncalderonAug 5, 2025
    Why is my Greenheck Ventilation Hood system showing negative pressure?
    • D
      David GayAug 5, 2025
      An unfavorable negative pressure condition in your Greenheck Ventilation Hood system may arise due to a few reasons. Begin by checking the BMS fan control to see if the condition occurs at the fan's low speed with the bypass fully open. Next, verify the power and signal at the duct pressure transducer(s). Finally, confirm the correct operation of the bypass damper.
  • N
    Nichole FosterAug 9, 2025
    How to fix Greenheck Vektor Ventilation Hood when fan runs but no pressure?
    • V
      vwheelerAug 9, 2025
      If the fan in your Greenheck Ventilation Hood is running but not creating pressure in the duct, there are a couple of things to check. First, make sure the isolation damper is open by checking its power. Also, verify that the bypass damper is closed.
  • C
    Chad MathisAug 14, 2025
    What to do if Greenheck Ventilation Hood nozzle actuator not responding?
    • C
      Cynthia SmithAug 14, 2025
      If the nozzle actuator on your Greenheck Ventilation Hood isn't responding to fan speed changes, check the following: Inspect the pressure tubing to the transducer and verify the voltages. Also, verify the power and signal at the actuator. Ensure that all laboratory hoods are open to verify nozzle operation, as low CFM due to closed hoods can cause this issue.
  • D
    Daniel WalkerAug 18, 2025
    How to stabilize fan speed on Greenheck Vektor?
    • T
      thomas62Aug 18, 2025
      If your Greenheck Ventilation Hood experiences unstable fan conditions where the fan isn't balancing the system and constantly changes speed, consider these solutions: Increase the time functions in the system to correct the BMS PID timing. Create an increased dead band between PID for the fan and bypass to address BMS PID overlap.
  • L
    Lisa DixonAug 22, 2025
    Why is the alarm active on Greenheck Vektor nozzle controller?
    • F
      Frank RobertsAug 22, 2025
      If the alarm contact on the nozzle controller of your Greenheck Ventilation Hood is active, it could be due to the velocity being below the required preset value, indicating the fan speed is too low and not creating enough airflow, so you should speed up the fan. It can also mean that airflow is not present, so check the flow station and components.

Summary

General Safety Information

VGN Control System Components

Quick Installation Guide

Connections

Instructions for connecting the VGN controller, pressure transducer box, and power wiring.

VGN System Function Overview

Controller to VFD and BMS Hardwiring

Fan Run Signal (hard wire connections)

Connecting the 24 VAC fan run input signal from BMS/VFD to the VGN controller.

BMS Communication (hard wire connections)

Wiring BMS for Nozzle Feedback, Fan Flow, and Alarm signals.

VGN Controller Incoming Power Wiring

BMS Communication Programming

Wiring Diagram - Single Fan

Wiring Diagram - Multiple Fans

Start-Up Procedure

Mechanical Component System Verification

Checklist for verifying fan assembly, fasteners, enclosures, alignment, and duct connections.

Electrical Control Components System Verification

Checklist for verifying fan rotation, damper operation, wiring, and BMS communication.

System Start-Up Preparation for VGN

Recommendations for having personnel on-site and ensuring readiness for VGN start-up.

System Start-Up for VGN

Step-by-step guide to applying power, checking controller, adjusting conditions, and verifying fan operation.

System Start-Up for VGN, continued

Steps to reduce fan speed, confirm nozzle adjustment, and verify system readiness.

Test and Balance for VGN

Test and Balance mode on the VGN controller

Using controller mode to lock nozzle position and adjust K value for CFM calibration.

Calibrating CFM Display

Test and Balance Procedure

Steps to calibrate CFM by offsetting the displayed value to match measured CFM.

VGN Controller Introduction and Tutorial

Operator Interface and Keypad Navigation

Description of controller buttons, screen layout, and basic navigation functions.

Keypad Navigation

Detailed explanation of the functions of each button: Escape, Up/Down, Alarm, Enter, Program.

Set Points Configuration

Test and Balance for Fan 1

Alarm History

Troubleshooting Guide

General

Table of common issues, possible causes, and recommended actions for general system operation.

VGN Nozzle Controller Customer-Supplied VFD

Troubleshooting specific to VFD issues and alarm conditions with the nozzle controller.

General System Failure Mode

Explains nozzle actuator behavior based on loss of 2-10 VDC signal or 24V power.

VGN Technology Maintenance

Electrical Replacement Parts

Greenheck Vektor Series Specifications

General IconGeneral
Fan TypeCentrifugal
MaterialStainless steel
CategoryVentilation Hood
BrandGreenheck
Drive TypeBelt-driven
MountingWall or ceiling
CertificationsUL
SeriesVektor
Control OptionsVariable speed control

Related product manuals