unit for each inverter in order to ensure that the inverter can be safely disconnected
under load.
We suggest you choice the AC breaker rating current in this table:
MIN 2500 TL-X
16A/230V
MIN 3000 TL-X
16A/230V
MIN 3600 TL-X
20A/230V
MIN 4200 TL-X
25A/230V
MIN 4600 TL-X
25A/230V
MIN 5000 TL-X
32A/230V
MIN 6000 TL-X
32A/230V
The AC wiring step:
1. Uninstall the parts of the AC connection plug from the accessory bag.
2. Insert the stripped and bared cable through pressure screw, seal ring, threaded sleeve in
sequence, insert cables into connection terminal according to polarities indicates on it and
tighten the screws firmly. Please try to pull out the wire to make sure the its well connected.