27
28
6.9 Connecting the COM PORT
This series inverter has a 8 Pin COM PORT, this port has the function fo demand response
modes, for Australian mode, we can use the 8 Pin COM PORT as inverter DRED
connection, for European modes, we can use the 8 Pin COM PORT as Power Control
Interface(PCI).
6.9.1 Inverter demand response modes-DRMs(Australia only)
This series inverter has the function of demand response modes, We use 8Pin COM PORT
as inverter DRED connection.
6.9.1.1 8Pin socket pin assignment
6.9.1.2 Method of asserting demand response modes
6.9.2 Inverter demand response modes-Power Control Interface(PCI) for EU
This series inverter has the function of demand response modes, We use 8Pin COM PORT
as Power Control Interface(PCI) for European models.
Active power control with a Radio Ripple Control Receiver(RRCR).
Information
CAUTION
DRMS application description
ØOnly applicable to AS/NZS4777.2:2015.
ØDRM0-DRM8 are available.
Damage to the inverter due to moisture and dust penetration
ØMake sure the cable gland has been tightened firmly.
ØIf the cable gland are not mounted properly, the inverter can
be destroyed due to moisture and dust penetration. All the
warranty claim will be invalid.
Pin
1
2
3
5
4
6
7
8
+12V
GND
DRM 1/5
DRM 2/6
DRM 3/7
DRM 4/8
RefGen
Com/DRM0
Assignment for inverters capable
of both charging and discharging
Mode
DRM 0
DRM 1
DRM 2
DRM 3
DRM 4
DRM 5
DRM 6
DRM 7
DRM 8
Socket Asserted by
shorting pins
Requirement
Operate the disconnection device
Do not consume power
Do not consume at more than 50% of rated power
Do not consume at more than 75% of rated power
Increase power consumption
Do not generate power
Do not generate at more than 50% of rated power
Do not generate at more than 75% of rated power
Increase power generation (subject to constraints from
other active DRMs)
7
1
2
3
4
1
2
3
4
8
8
8
8
8
7
7
7
7
WARNING
Excessive voltage can damage the inverter!
External voltage of PCI PORT don't over +5V.