Growatt New Energy Australia Pty Ltd
C1, 27-29 Fariola Street,
Silverwater NSW 2128
Fig 1.4 ShineCHK
Increase voltage range via shinewifi
Basically we have two method to increase the voltage range, one is via ShineWifi and the
other is via software Shinebus.
a) Change it remotely via Wi-Fi module monitoring
If the inverter had been monitored by Growatt Wi-Fi module, then the setting can be
changed via computer/laptop remotely. ShineServer set inverter tripping voltage Vmax
Please follow the below steps to change the tripping voltage Vmax settings via ShineServer:
(1) After signed in, click Plant -> Device List, then click inverter. A list of monitored inverter
under the monitoring would then available.
(2) In the right side, operating field, click the SET symbol to open the Inverter setting
interface.
(3) Choose the option “Set grid voltage high”, and fill in the value. We suggest changing it to
268 volt.