Address Register name Description
00213 MinFrequency
Minimum pump frequency in % of nominal frequency. The scale is 0.01 %.
Only available on MAGNA3 and MGE model H and later.
00214 MaxFrequency
Maximum pump frequency in % of nominal frequency. The scale is 0.01 %.
Only available on MAGNA3 and MGE model H and later.
00215 SetpointRangeMin
Minimum value of setpoint range in % of sensor maximum value. The scale is 0.01 %.
Only available on MAGNA3 and MGE model H and later.
00216 SetpointRangeMax
Maximum value of setpoint range in % of sensor maximum value. The scale is 0.01 %.
Only available on MAGNA3 and MGE model H and later.
00217 RESERVED -
00218 RESERVED -
00219 RESERVED -
00220 RESERVED -
00221 FlowEstimationState
State of the flow estimation algoritm
0: Flow estimation within range
1: Flow estimation below range
2: Flow estimation above range
00222 Kp
Actual proportional gain. The scale is 0.1.
Only available on MAGNA3 and MGE model H and later.
00223 Ti
Actual integral action time. The scale is 0.1 s.
Only available on MAGNA3 and MGE model H and later.
00224 DirectControl
Actual selection between Direct/Inverse control.
0: Inverse control
1: Direct control
Only available on MAGNA3 and MGE model H and later.
Related information
9.2 CIM configuration register block
17. Grundfos alarm and warning codes