EasyManua.ls Logo

Grundfos CIU 500 - Status Leds

Grundfos CIU 500
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English (GB)
12
6.2 Status LEDs
The CIM 250 GSM module has two LEDs. See fig. 12.
Yellow/green status LED (LED1) for GSM/GPRS
communication.
Red/green status LED (LED2) for internal communication
between the CIM 250 and the E-pump.
LED1 (yellow/green)
Fig. 16 LED1 status
LED2 (red/green)
TM04 5194 4412
Pos. Status Description
1 Flashing yellow Searching for GSM network.
2
Pulsating yellow
(single pulse)
Connection to the GSM network
has been established.
3 Constantly yellow
Call-up connection has been
established.
4
Pulsating green
(single pulse)
Data are exchanged via GPRS.
5
Pulsating green
(double pulse)
Data are exchanged via the call-up
connection.
6 Green (3 sec.)
Sending or receiving an SMS
message.
Status Description
Off The CIM 250 has been switched off.
Flashing red
No communication between the CIM 250
and the E-pump.
Constantly red
The CIM 250 does not support the
connected version of the E-pump.
Constantly green
The connection between the CIM 250 and
the E-pump is OK.