EasyManua.ls Logo

Grundfos IO 351 - Overview of Inputs and Outputs; Terminal Designations and Diagrams

Grundfos IO 351
27 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9. Overview of inputs and outputs
DI: Digital input
DO: Digital output
AO: Analog output
AI: Analog input
NO: Normally open contact
C: Common
Group Terminal Designation Data Diagram
1
L
Connection of phase
conductor
1 x 100-240 VAC ± 10 %, 50/60
Hz
IO 351
L
N
L
N
PE
L
N
Connection of neutral
conductor
N
PE
Connection to protec-
tive earth
PE
2
76 DO 1, 2, 3, C
Relay contact, NO.
Maximum load: 240 VAC, 2A
Minimum load: 5 VDC, 10 mA
IO 351
76
76
-77
-79
-81
76 DO 1, 2, 3, C
77 DO 1, NO
79 DO 2, NO
81 DO 3, NO
3A
53 + 24 V
Supply to sensor. Maximum 50
mA
IO 351
53
55
57
60
1
2
55 GND
57 AI 1
Input for analog signal, 0/4-20
mA or 0-10 V
60 AI 2
All terminals (except mains terminals) must only be connected to
voltages not exceeding 16 Vrms and 22.6 Vpeak or 35 VDC.
3A
10 DI 1
Digital input
12 DI 2
14 DI 3
15 GND
All terminals (except mains terminals) must only be connected to
voltages not exceeding 16 Vrms and 22.6 Vpeak or 35 VDC.
13
English (GB)

Related product manuals