English (GB)
24
9.3.1 Checking input and outputs
Pt100/1000
Use a 100 Ω resistance and decide on the basis on the motor 
settings which value this resistance will show in the display when 
connected to the terminals instead of the Pt100/1000 sensor.
Analog input, AI
It is possible to measure on the analog input to determine if its 
function is correct.
During current state, a 292 Ω resistance in the input converts a 
current signal (e.g. 0-20 mA) from the sensor to a voltage signal 
for the processor.
Measure the voltage across the input and read the current in the 
circuit by means of Grundfos GO Remote or PC Tool. The current 
value must be equal to voltage divided with resistance. 
Alternatively, a milliammeter can be connected in series with the 
circuit.
Fig. 55 Measuring on analog input
Next step is to test the input in voltage state. Change the setup of 
the input to voltage state (0-10 V). Fit a jumper between terminal 
5 (+5 V) and the analog input. 5 V must now be read be means of 
PC Tool.
Fig. 56 Testing the input during voltage state
Change the setup of the input to current state and measure on 
the input using an ohmmeter. The resistance must be 292 Ω. In 
voltage state, the resistance is 122 kΩ.
Fig. 57 Measuring resistance in current and voltage state
Analog output, AO
The analog input is protected against short circuit and will shut 
down the signal in case of short circuit. If you suspect a short 
circuit, remove the load and compare the value read via PC Tool 
with the value measured by means of the measuring instrument.
If the values are not identical, the module is defective.
Digital input, DI
See the settings of the input in PC Tool.
Connect the digital input to frame (GND) by means of an 
ammeter. The value measured must now be approximately 12 
mA. Check that PC Tool shows a corresponding value.
Fig. 58 Testing the digital input
Digital output, DO/open collector, OC
See the settings of the output in PC Tool.
Measure the output. If the value in PC Tool differs from the value 
measured with the measuring instrument, remove the load. If the 
values still differ, the module is defective.
The voltage of an active output is approximately 5 V.
Fig. 59 Measuring voltage on the digital output
LiqTec sensor
Connect a new LiqTec sensor to check the input. Immerse the 
sensor into water and take it up. The motor must now report fault 
within 20 seconds.
Signal relay
See the settings of the output in PC Tool.
Check if the relay reacts to the signals of the controller according 
to the configuration of the controller.
CIM
Test the CIM module according to its manual.
Radio
If there are problems in the radio connection between Grundfos 
GO Remote and the motor, remove the terminal box cover. See 
section 7.1 Replacing the terminal box cover. Replace the control 
panel if there is still no connection. See section 7.4 Replacing the 
control panel.
Battery
Switch off power to the motor for a short period. When you switch 
on the power to the pump again, adjust the clock.
Control panel (HMI)
Check the flat cable to the functional module. Replace the control 
panel if the connection is correct, and it did not solve the problem.
Make a copy of motor settings.