EasyManua.ls Logo

Grundfos UP15-42F - Dip Switch Configuration

Grundfos UP15-42F
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 7
Page 7
Setting Dip Switches
Figure 7A -
Dip Switches
Dip switch settings
POSITION
Feature Explanation
Dip switch C - minimum speed off/minimum speed
15%. When dip switch C is in the ON position the
variable speed of the pump will have a range from
minimum speed = off to maximum speed = 100%.
When dip switch C is in the OFF position the variable
speed of the pump will have a range from minimum
speed = 15% to a maximum speed = 100%.
Dip switch D - speed control external/speed control
maximum % dial. When dip switch D is in the ON
position an external V(dc)/mA signal will cause the
pump speed to vary and the dial on the terminal box
will function in the -5% to +5% mode. When dip switch
D is in the OFF position turning the manual % dial will
vary the pump speed. The pump will not respond to an
external V(dc)/mA signal even if one is present. The
terminal box and the dial will function in the minimum
to 100% mode.
7. Settings
ON
OFF DEFAULT
SWITCH
mA
(V) DC mA
0-10V
0-20mA
2-10V
4-20mA
min speed
15%
min speed
off
speed control
external
2-10V
4-20mA
min speed
off
speed control
manual % dial
speed control
external
A
B
C
D
6.
Settings
Setting Dip Switches:
Figure 5 -
Dip Switches
Dip Switch Settings:
Feature Explanation
Dip Switch C - minimum speed off/minimum speed
15%. When dip switch C is in the ON position the
variable speed of the pump will have a range from
minimum speed = off to maximum speed = 100%.
When dip switch C is in the OFF position the variable
speed of the pump will have a range from minimum
speed = 15% to a maximum speed = 100%.
Dip Switch D - speed control external/speed control
maximum % dial. When dip switch D is in the ON
position an external V(dc)/mA signal will cause the
pump speed to vary and the dial on the terminal box
will function in the -5% to +5% mode. When dip switch
D is in the OFF position turning the manual % dial will
vary the pump speed. The pump will not respond to an
external V(dc)/mA signal even if one is present. The
terminal box and the dial will function in the minimum
to 100% mode.
Page 7
Setting Dip Switches
Figure 7A -
Dip Switches
Dip switch settings
POSITION
Feature Explanation
Dip switch C - minimum speed off/minimum speed
15%. When dip switch C is in the ON position the
variable speed of the pump will have a range from
minimum speed = off to maximum speed = 100%.
When dip switch C is in the OFF position the variable
speed of the pump will have a range from minimum
speed = 15% to a maximum speed = 100%.
Dip switch D - speed control external/speed control
maximum % dial. When dip switch D is in the ON
position an external V(dc)/mA signal will cause the
pump speed to vary and the dial on the terminal box
will function in the -5% to +5% mode. When dip switch
D is in the OFF position turning the manual % dial will
vary the pump speed. The pump will not respond to an
external V(dc)/mA signal even if one is present. The
terminal box and the dial will function in the minimum
to 100% mode.
7. Settings
ON
OFF DEFAULT
SWITCH
mA
(V) DC mA
0-10V
0-20mA
2-10V
4-20mA
min speed
15%
min speed
off
speed control
external
2-10V
4-20mA
min speed
off
speed control
manual % dial
speed control
external
A
B
C
D

Related product manuals