EasyManua.ls Logo

Haes Excel-EN - Addressing

Default Icon
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
19
SETUP & PROGRAMMING
Programming
The Master panel will need to be programmed for the number of network panels on the system. See panel
wide programming settings, code 2-1-2-3, option 10, (Set Number of Network Slave Panels on System).
Addressing
Each panel needs to have a unique address. The addressing is done using the 4 DIL switches on each of
the Comms PCBs using binary code values, see diagram below.
The addresses should be set in sequence from 1 - 8, rst slave panel = address 01, second slave panel =
address 02 etc.
The Master panel is de ned by being address 00 (all switches off).
Network slave panels and/or repeater panels are designed to be wired in a fault tolerant (fail safe) loop
con guration, from comms A to B and back to the Master panel again (see drawing below). This enables
the network to still function if there is a break in the cables.
If replacing an older system where the existing cabling cannot be con gured in a loop as above, it is
possible to change the panel settings to legacy, radial circuit comms monitoring.
See panel wide programming settings, code 2-1-2-3, option 6, (Change Network/Repeater Comms
Monitoring Type).
1 2 34
ON
ADD 01
1 2 34
ON
ADD 02
1 2 34
ON
ADD 03
1 2 34
ON
ADD 04
1 2 34
ON
ADD 05
1 2 34
ON
ADD 06
1 2 34
ON
ADD 07
SLAVE PANEL 1
SLAVE PANEL 5 SLAVE PANEL 6 SLAVE PANEL 7
1 2 34
ON
ADD 00
MASTER PANEL
SLAVE PANEL 2 SLAVE PANEL 3 SLAVE PANEL 4
COMS A COMS B 28
V+
SW -ve OUTPUTS
+-
+-
12345 6
1 2 34
ON
ADDRESS
COMS A COMS B 28
V+
SW -ve OUTPUTS
+-
+-
12345 6
1 2 34
ON
ADDRESS
COMS A COMS B 28
V+
SW -ve OUTPUTS
+-
+-
12345 6
1 2 34
ON
ADDRESS
Fault Tolerant Loop Wiring
Master Panel Slave/Repeater Panel 1 Slave/Repeater Panel 2

Related product manuals