EasyManua.ls Logo

Haes Excel-EN - Zone Interface Function

Default Icon
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
21
SETUP & PROGRAMMING
This setting con gures the last zone on the panel, (i.e. zone 2 on a 2 zone, zone 4 on a 4 zone, zone 6
on a 6 zone, zone 8 on an 8 zone and zone 12 on a 12 zone), to be used for interconnection from other
control panels.
It is possible, in the Level 3 engineering programming, to setup any zone for this function, however, this is
simply a shortcut method.
The function is enabled by setting switch 5 on the 7 way DIL
switch located on the main PCB to the ‘ON’ position.
With switch 5 in the ‘ON’ position, the last zone becomes;
1.
1.
Non latching &
Non latching &
2.
2.
Non aux operating.
Non aux operating.
Note:
If the interface zone is also set to Twin Wire mode and sounders are connected to the zone circuit, the
following sounder operation will apply:
A re (470Ω) signal to the interface zone will NOT operate the sounders connected to that Twin Wire circuit.
All other conventional (SNDR1 & SNDR2) and Twin Wire zone sounders will operate as normal.
A re (470Ω) signal to any other zone will operate ALL conventional (SNDR1 & SNDR2) and Twin Wire
sounder circuits, including the sounders connected to the interface zone, as normal.
ZONE INTERFACE FUNCTION
1 2 345
67
ON
+-+- +-
ZONE2 ZONE3 ZONE4
CNCNO
NO
CNC
FIRE
FAULT
(optional)
PANEL 1 PANEL 2
470Ω
3K3Ω
Example connection

Related product manuals