Service diagnosis
7.4.10 Power Supply over or under voltage fault
Indoor display            F19 
 
Outdoor display:          LED1 flash 6 times
             5"#)#$#!6!
Domestic air conditioner
Method of 
malfunction 
detection 
Malfunction 
detection 
conditions 
Supposed 
causes
 
Troubleshooting 
'  
Be sure to turn off power switch before connect or disconnect connector, or 
else 
parts damage may be caused 
ƵSupply voltage not as specified 
ƵThe IPM module is broken. 
Ƶ The outdoor PCB is broken.
An abnormal voltage rise or fall is detected by specified voltage checking 
detection circuit
An voltage signal is feedback from the voltage detection circuit to the 
microcomputer
NO 
House power supply fault. 
Change the new one 
Change the outdoor PCB 
Is it rated value? 
NO 
YES 
YES 
Check the power supply
 
Check the IPM 
module, Is it normal?