Functions and control 
15  Domestic air conditioner
7. Functions and control
7.1 Main functions and control specification 
7.1.1 The operation frequency of outdoor unit and its control 
7.1.1.1 The operation frequency control of compressor
The operation frequency scope of compressor
Mode  Minimum operation frequency  Maximum operation frequency 
Heating 09K
32Hz  75Hz 
Refrigeration 09K
7.1.1.2 The starting of compressor 
When  the  compressor  is  started  for  the  first  time,  it  must  be  kept  under  the  conditions  of 
38Hz,58Hz,88Hz for 30second,one minute, one minute (the overheating protection of the outdoor unit 
air-blowing temperature, immediately decrease the frequency when the compressor is overflowing and 
releasing the pressure)
then it can be operated towards the target frequency. When the machine runs 
normally, there’s no such process. After starting the compressor for operation, the compressor should 
run according to the calculated frequency, and every determined frequency for protection should be 
prior to the calculated frequency.   
7.1.1.3 The speeds of increasing or decreasing the frequency of the compressor 
The speed of increasing or decreasing the frequency rapidly 1 -----------1HZ/second 
The speed of increasing or decreasing the frequency slowly 2 -----------1HZ/10seconds
7.1.1.4 The calculation of the compressor’s frequency 
Refrigeration/dehumidification mode: 
Pn=(Nh_c- S_c)*10 50  outdoor environment control 
Pn=(Nh_c- S_c) *10 50  PID control 
Heating mode: 
Pn=(S_c
 -Nh_c) *10 60  outdoor environment control 
Pn=(S_c
 -Nh_c) *10 60  PID control 
(Nh_c=indoor environment    temperature  S_c=setting temperature) 
1
The minimum/maximum frequency limitation 
A
While refrigerating: F-MAX-r is the maximum operation frequency of the compressor; F-MIN-r is the 
minimum operation frequency of the compressor. 
B
While heating: F-MAX-d is the maximum operation frequency of the compressor; F-MIN-d is the 
minimum operation frequency of the compressor. 
2
The frequency limitation which is affected by the environment temperature. 
(Wh_c= environment temperature) 
Heating mode: 
Serial No.  Temperature scope 
Frequency limitation
09K
1  Wh_c<-12  Max_hz1      99HZ
2  Wh_c<-8  Max_hz2      99HZ
32Hz  99 Hz