EasyManua.ls Logo

Haier 1U35YEFFRA-C - Page 360

Haier 1U35YEFFRA-C
537 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions and control
18 Domestic air conditioner
state). TC=indoor coil temp.
The indoor heat exchanger sensor tests the temperature of the indoor heat exchanger. If the
temperature is higher than 63 , decrease the rotate speed of the compressor and do the high
temperature-preventing protection of the indoor heat exchanger; if the temperature of the indoor heat
exchanger is lower than 4
5, recover to the normal control.
(09K12K)
TC() The compressor stops Fgh_t1 63/63
Fgh_t12
Fgh_t22 N Decreasing the frequency rapidly Fgh_t2 60/59
P Decreasing the frequency slowly Fgh_t3 57/56
Fgh_t32
Fgh_t4—2 Q Prohibiting increasing the frequency Fgh_t4 52/53
R Increasing slowly Fgh_t5 40/40
Fgh_t5—2
Normal
NDecreasing at the speed of 1HZ/1 second
PDecreasing at the speed of 1Hz/10 seconds
QContinue to keep the last-time instruction cycle
RIncreasing at the speed of 1Hz/10seconds
Remarks: the outdoor unit
7.1.5.3 The control of preventing the over current of the compressor:
During the starting process of the compressor, if the current of the compressor is greater than 12.5A
for 3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3 times
in 20 minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to run it only
after the power is off.
During the starting process of the compressor, if the AC current is greater than 9A, the frequency of
the compressor decreases at the speed of 1HZ/second.
During the starting process of the compressor, if the AC current is greater than 8A, the frequency of
the compressor decreases at the speed of 0.1HZ/second.
During the starting process of the compressor, if the AC current is greater than 7.5A, the frequen
cy of
the comp
ressor increases at the prohibited speed.
During the starting process of the compressor, if the AC current is greater than 6.5A, the frequen
cy of
the comp
ressor increases at the speed of no faster than 0.1HZ/second.
7.1.5.4 The protection function of AC current:
During the starting process of the compressor, if the AC current is greater than 12.5A for 3 seconds,
stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3 times in 20 minutes,
stop the compressor and alarm, and confirm the malfunction. Then continue to run it only after the the
power is off.
During the starting process of
the compressor, if the AC current is greater than 9A, the frequency of the
compressor decreases at the speed of 1HZ/second.
During the starting process of the compressor, if the AC current is greater than 8A, the frequency of the
compressor decreases at the speed of 0.1HZ/second.
During the starting process of the compressor, if the AC current is greater than 7.5A, the frequency of

Table of Contents

Other manuals for Haier 1U35YEFFRA-C

Related product manuals