Functions and control
14                   Domestic air conditioner 
7.Funcitions and control 
7.1 Main functions and control specification
7.1.1  Automatic operation 
When the running mode is turned to automation after starting the system, the system will first 
determine the running mode according to the current room temperature and then will run according to 
the determined mode. Tr in the following selection conditions means room temperature, Ts means 
setting temperature, Tp means temperature of indoor coil pipe       
TrıTs-3ć     Choose Cooling Mode 
Tr˘Ts-3ć    Choose Heating Mode 
After turning to the automation mode, the running mode can be switched between cooling mode, 
fan mode and heating mode according to the change of the indoor ambient temperature. But the 
automatic conversion between cooling mode and heating mode must be conducted after 15 minutes.
7.1.2  Cooling operation mode 
Temperature control range:  16ć---30ć
Temperature difference:     r1ć
* Control features: When Tr˄input airflow˅>Ts˄set temperature˅+ temperature Backlash A, the 
compressor will be opened, the indoor fan will operate at the set speed and the mode signal will be 
sent to the outdoor system. When Tr˄input airflow˅ Ts˄set temperature˅ temperature Backlash 
B, the compressor will be shutted, the indoor fan will operate at the set speed and the mode signal will 
be sent to the outdoor system. The system will keep the original status if Tr= Ts. 
Airflow speed control: (temperature difference 1ć)
Automatic: When TrTs+ 3ć, high speed. 
          When Ts+1ćTr<Ts+3ć, medium speed 
          When Tr<Ts+1ć, low speed 
          When the sensor is off, low speed 
When the airflow speed has no delay from the high to low switching, the speed should be delayed for 
3 minutes (remain at high speed for 3 minutes.) before the next switch. 
Manus: When the system is operating, you can set the high, medium or low speed manually. (When 
the sensor is on or off, the system will change the speed 2 seconds after receiving the signal.) 
*Airgate location control: the location for the airgate can be set according to your needs. 
*Defrosting function: preventing the frosting on the indoor heat exchanger (when cooling or 
dehumidifying). When the compressor works continuously for 6 minutes and the temperature of the 
indoor coils has been below one centigrade for 10 seconds, the compressor will be stopped and the 
malfunction will be recorded in the malfunction list. The indoor system will continue to run. When the 
temperature of the indoor coil is raised to 9ć, the compressor will be restarted again (the requirement 
of 3 minutes’ delay should be satisfied.) 
* timing system on/off function. 
* Dormant control function.