Service diagnosis 
45  Domestic air conditioner 
10.3.12 High work-intense protection 
Outdoor display  LED1    flash 21 times
 
 
 
Method of 
High work-intense control is activated in the heating mode if the temperature 
Malfunction   
being sensed by the heat exchanger ther
●
mistor exceeds the limit. 
Detection 
Malfunction 
Activated when the temperature being sensed by the heat exchanger 
●
Decision 
rises above 65℃ twices in 30 minutes. 
Conditions 
Supposed 
■
Faulty electronic expansion valve
Causes 
■
Dirty heat exchanger
■ Faulty heat-exchange sensor
■ Insufficient gas
Troubleshooting 
* Caution   
Be sure to turn off power switch before connect or disconnect connector,      or else
parts damage may be occurred. 
Electrify the  machine  again  and turn it  on  with  the 
remote  controller,  check  whether  the  wind 
temperature is below 65℃ 
The  malfunct
●
ion  is  reported 
after  the  machine  has  run 
1 、 Check  room  temperature  and 
pipe temperature sensor. 
2、the temperature monitoring circuit 
of the indoor mainboard   
T
●
he indoor unit blows poorly 
due to blocked filters or poor 
1) Clean the filters
2) Reinstall the fan.
Use some tools to measure the pressure of system, 
YES 
NO 
YES 
NO