Loading and Unloading/Transporting Management/Storage Requirements 
1) The products shall be carefully handled during loading and unloading.
2) Rude  and  barbarous  handling  such  as  kicking,  throwing,  dropping,  bumping,  pulling  and  rolling  is  not
allowed.
3) The  workers  engaged  in  loading  and  unloading  must  be  subject  to  necessary  trainings  on  the  potential
hazards caused by barbarous handling.
4) Dry powder extinguishers or other suitable fire extinguishing apparatus within the period of validity shall be
equipped at the loading and unloading site.
5) The  untrained  personnel  cannot  be  engaged  in  loading  and  unloading  of  flammable  refrigerants  air
conditioner.
6) Before loading and unloading, anti-static measures shall be taken, and phones cannot be answered during
loading and unloading.
7) Smoking and open fire are not allowed around the air conditioner.
Transporting Management Requirements
1) The maximum transporting volume of finished products shall be determined as per local regulations.
2) The vehicles used for transporting shall be operated as per local laws and regulations.
3) Dedicated  after-sales  vehicles  shall  be  used  for  maintenance,  and  exposed  transporting  of  refrigerant
cylinders and the products to be maintained is not allowed.
4) The rain cover  or  similar shielding material of  transporting vehicles shall be provided  with  certain flame
retardancy.
5) Leakage warning device of flammable refrigerant shall be installed inside the closed-type compartment.
6) Anti-static device shall be equipped inside the compartment of transporting vehicles.
7) Dry powder extinguishers or other suitable fire extinguishing apparatus within the period of validity shall be
equipped inside the driver's cab.
8) Orange-white or red-white reflective stripes shall be pasted on the sides and tail of the transporting vehicles,
to remind the vehicles behind of keeping distance.
9) The transporting vehicles shall run at a constant speed, and heavy acceleration/deceleration shall be avoided.
10) Combustibles or the static articles cannot be transported simultaneously.
11) High-temperature area shall be avoided during transporting, and necessary radiating measures shall be taken
in case the temperature inside the compartment is too high.
Storage Requirements
1) The storage package of equipment used shall be such that no leakage of refrigerant will be caused due to
m
echanical damage of the equipment inside.
2) The  maximum  quantity  of  the  equipment allowed to  be  stored  together  shall  be  determined  as  per  local
regulations.
Installation 
Instructions 
WARNING! 
  The area of the room in which R32 refrigerant air conditioner is installed cannot be less than the minimum 
area  specified  in  the  table  below,  to  avoid  potential  safety  problems  due  to  out-of-limit  of  refrigerant 
concentration inside the room caused by leakage of refrigerant from refrigeration system of the indoor unit.  
  Once the horn  mouth  of  connecting lines  is  fastened,  it  may not be  used again  (the air tightness  may be 
affected). 
  A whole connector wire shall be used for indoor/outdoor unit as required in the operation specification of 
installation 
The values of The maximum refrigerant charge amount are shown in table 2
process and operation instructions.  
Minimum Room Area 
Type
LFL
kg/m3 
Total Mass Charged/kg 
Minimum Room Area/m
2
R32  0.306 
  1.224  1.836  2.448  3.672  4.896  6.12  7.956 
3  6  13  23  36  60 
3