1) Fixation
The support of the outdoor unit shall be fixed onto the wall surface, and then the outdoor unit shall be fixed onto
the support horizontally. In case the outdoor unit is wall-mounted or roof-mounted, the support shall be firmly
fixed, to avoid the damage of strong wind.
2)
Installation of 
connecting pipes
The cone of the connecting pipes shall be aligned with the conical surface of corresponding valve connector.
The nut of connecting pipes shall be installed at a proper position and then be tightened with a spanner. Excessive
tightening torque shall be avoided, or otherwise the nut may be damaged.
•
Vacuumizing
A di
gital vacuum gauge shall be connected for vacuumizing. The duration of vacuumizing shall be at least 15
minutes, and the pressure of the vacuum gauge shall be below 60Pa.Afterwards, the vacuumizing equipment shall 
be closed, and whether the reading of the digital vacuum gauge is increased or not shall be observed after the 
pressure is maintained for 5 minutes. In case no leakage is identified, the two-way stop valve and three-way stop 
valve of the outdoor unit may be opened. Finally, the vacuumizing hose connected to the outdoor unit can be 
disassembled.  
• Leak Detection
The joint of connecting pipes for the outdoor unit shall be subject to leak detection with soap bubble or
dedicated leak detection equipment.  
• Post-installation Inspection Items and Test Run
Post-installation Inspection Items 
Items to Be Checked  Consequence of Improper Installation 
Whether the installation is firm or not  The unit may fall, vibrate or make a noise 
Whether the inspection on air leakage is completed The refrigerating capacity (heating capacity) may be 
insufficient 
Whether the unit is fully insulated  Condensation or drip may occur 
Whether the drainage is smooth or not  Condensation or drip may occur 
Whether the power voltage is identical to that 
marked on the nameplate 
Failure may occur or the parts may be burned 
Whether the circuit and pipeline are installed 
correctly 
Failure may occur or the parts may be burned 
Whether the unit is safely earthed  Electric leakage may occur 
Whether the type of wire is in line with relevant 
regulations 
Failure may occur or the parts may be burned 
Whether barriers are identified at the air inlet/outlet 
of the indoor/outdoor unit 
The refrigerating capacity (heating capacity) may be 
insufficient 
Whether the length of refrigerant pipes and the 
refrigerant amount charged are recorded 
The refrigerant amount charged cannot be confirmed 
Test Run 
1. Preparations
(1) Power on is not allowed before all the installation operations are completed and before the leak
detection is proven qualified.
(2) The control circuit shall be connected correctly and all the wires shall be firmly connected.
(3) The two-way stop valve and three-way stop valve shall be opened.
(4) All the scattered articles (especially the metal filing and thread residue) shall be removed from the unit
body.
2. Methods
(1) Switch on the power supply and press the “ON/OFF” on the remote controller, after which the air
conditioner will start operating.
(2) Press “Mode” to select refrigeration, heating and sweeping wind, and observe whether the air
conditioner is under normal operation.
6