EasyManua.ls Logo

Haier AB25S2SC1FA - Page 35

Haier AB25S2SC1FA
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
For AD50S2SM1FA/AD71S2SM1FA
Installation procedure
1. Applicable ambient temperature range:
The machine is adaptive in following situation
Cooling
Heating
Indoor temperature
Outdoor temperature
Indoor temperature
Outdoor temperature
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
32/23 C
18/14 C
46/26 C
10/6 C
27 C
15 C
24/18 C
-15 C
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.
3. If the fuse on the indoor PC board is broken please change it with the type of T 6.3A /250VAC(For series 24,28,36,48).
4. The wiring method should be in line with the local wiring standard.
5. The power cable should be:
H05RN-F 3G 4.0mm
2
;
The connecting cable should be:
H05RN-F 4G 2.0mm
2
All the cables shall have got the European authentication certificate. During installation, when the connecting cables
break off, it must be assured that the grouding wire is the last one to be broken off.
6. The power cable and conne
ct cable should be self-provided.
7. The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be no
less than 3mm.
8. The indoor unit installation height is at least 2.5m.
9. A leakage breaker must be installed.
10.
For AD50S2SM1FA AD71S2SM1FA
,we can get the 10 different ESP through adjust wired controllerYR-E17,please refer
below:
AD50S2SM1FA AD71S2SM1FA
Stacc pressure
grade
1 2 3
5
4
7
6
8 9 10
Stacc pressure 25Pa 37Pa 50Pa 70Pa 90Pa 100Pa 110Pa 120Pa 130Pa 150Pa
Adjsutment metchod bywired controller YR-E17In the state of ON and non screen saving state, press Fan+ Set keys for
5s to enter stac pressure grade adjustmentstate with stac pressure icon flashing and current stacpressure grade
stacally displaying. Press key↑↓ to changestac pressure grade, then press Set key to conrm.
Details please refer to wired controller operaon & installaon manual.
Adjsutment metchod by Infrared remote controller+Infrared receiver RE-02Step a:set the Infrared remote controller at
condion FAN mode fan speed high Step b:then aim the remote contr
oller at the infrared remote receiver RE-02
press HEALTH buon 4+N mes1N10integerwithin 12 seconds then the receiver will beep N+1 mes the
stac pressure level N is been set successfully.
NoteFor Infrared remote controller YR-HBS01, need press ON/OFF buon make the controllers at OFF status rstthen
open the buon cover press FRESH buon will enter FAN mode interface.

Other manuals for Haier AB25S2SC1FA

Related product manuals