199
AB71S2SG1FA
PCB 0151800208CE dip switch setting SM1
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8 Description
ON ON OFF -- -- -- -- -- AB71S2SG1FA
-- -- -- OFF -- -- -- -- Room Card Valid (Default)
-- -- -- ON -- -- -- -- Room Card Invalid
-- -- -- -- OFF -- -- -- Cool and Heat (Default)
-- -- -- -- ON -- -- -- Cool Only
-- -- -- -- -- OFF ON OFF
PCB 0151800208CE dip switch setting:
Indoor unit address setting in wired controller group control BM3 (SW3)
BM3-8 BM3-7 BM3-6 BM3-5 Description
OFF OFF OFF OFF Master indoor unit
OFF OFF OFF ON 1# Slave Indoor Unit
OFF OFF ON OFF 2# Slave Indoor Unit
OFF OFF ON ON 3# Slave Indoor Unit
OFF ON OFF OFF 4# Slave Indoor Unit
OFF ON OFF ON 5# Slave Indoor Unit
OFF ON ON OFF
6# Slave Indoor Unit
OFF ON ON ON
7# Slave Indoor Unit
ON OFF OFF OFF
8# Slave Indoor Unit
ON OFF OFF ON
9# Slave Indoor Unit
ON OFF ON OFF
10# Slave Indoor Unit
ON OFF ON ON
11# Slave Indoor Unit
ON ON OFF OFF
12# Slave Indoor Unit
ON ON OFF ON
13# Slave Indoor Unit
ON ON ON OFF
14# Slave Indoor Unit
ON ON ON ON
15# Slave Indoor Unit