61
Item                                                                                  Model AD50S2SM1FA
Function —— Cooling Heating
Capacity W 5000 6000
Sensible heat ratio W 0.73 /
Dehumidifying capacity 10-³xm³/h 1.8 
Indoor unit
Power supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*2
Speed(H-M-L) r/min 900/820/770/720
Fan motor output/input power W 45/70
Air-ows (H-M-L) m³/h 1080/900/780/660
External static pressure Pa
25/37/50/70/90/
100/110/120/130/150
Heat exchanger
Type / Diameter mm Inner grooved pipe/φ7.0
Row —— 2
Total area m² /
Temp.scope °C 2.0-7.0
Dimension 
(LxWxH)
External mmxmmxmm 957/655/250
Package mmxmmxmm 1170/860/340
Drainage pipe (Material,I.D/O.D) mm PVC  25/29
Control type(Remote/Wired) Wired YR-E17(O) or Remote YR-HBS01(O)
Fresh air hole dimension mm 145
Electricity heater kW None
Noise level
(H-M-L)
Sound power level dB(A) 57
Sound pressure level dB(A) 37/34/32/29
Weight(Net/Shipping) kg/kg 26/33
Piping
Refrigerant Type  R32 
Pipe
Liquid mm Φ6.35(1/4)
Gas mm Φ12.7(1/2)
Connecting method Flared
Norminal condition: indoor temperature (cooling): 27°CDB/19°CWB, indoor temperature (heating): 20°CDB 
Outdoor temperature(cooling): 35°CDB/24°CWB, outdoor temperature(heating): 7°CDB/6°CWB 
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound 
intensity meter.