EasyManua.ls Logo

Haier AD140S2SM3FA - Page 64

Haier AD140S2SM3FA
257 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
61
Item Model AD50S2SM1FA
Function —— Cooling Heating
Capacity W 5000 6000
Sensible heat ratio W 0.73 /
Dehumidifying capacity 10-³xm³/h 1.8
Indoor unit
Power supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*2
Speed(H-M-L) r/min 900/820/770/720
Fan motor output/input power W 45/70
Air-ows (H-M-L) m³/h 1080/900/780/660
External static pressure Pa
25/37/50/70/90/
100/110/120/130/150
Heat exchanger
Type / Diameter mm Inner grooved pipe/φ7.0
Row —— 2
Total area /
Temp.scope °C 2.0-7.0
Dimension
(LxWxH)
External mmxmmxmm 957/655/250
Package mmxmmxmm 1170/860/340
Drainage pipe (Material,I.D/O.D) mm PVC 25/29
Control type(Remote/Wired) Wired YR-E17(O) or Remote YR-HBS01(O)
Fresh air hole dimension mm 145
Electricity heater kW None
Noise level
(H-M-L)
Sound power level dB(A) 57
Sound pressure level dB(A) 37/34/32/29
Weight(Net/Shipping) kg/kg 26/33
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ6.35(1/4)
Gas mm Φ12.7(1/2)
Connecting method Flared
Norminal condition: indoor temperature (cooling): 27°CDB/19°CWB, indoor temperature (heating): 20°CDB
Outdoor temperature(cooling): 35°CDB/24°CWB, outdoor temperature(heating): 7°CDB/6°CWB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound
intensity meter.

Other manuals for Haier AD140S2SM3FA

Related product manuals