EasyManua.ls Logo

Haier AD140S2SM3FA - Page 66

Haier AD140S2SM3FA
257 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
63
Item Model AD71S2SM1FA
Function cooling heating
Capacity KW 7.1(2.0~8.2) 8.0(2.5~8.5)
Sensible heat ratio 0.74 /
Total power input KW 2.15(0.6~2.6) 2.16(0.6~2.6)
Max. power input W 3000 3000
EER or COP W/W 3.30 3.71
Dehumidifying capacity 10
-
³×m³/h 2.5
Power cable H05RN-F 4G 6.0mm2
Power source N, V, Hz 1PH, 220-240V~, 50/60Hz
Running /Max.Running current A / A 9.7(2.3-12)/16 9.8(2.3-12)/16
Start Current A 3
Indoor unit
Unit model (color) AD71S2SM1FA
Fan
Type × Number Centrifugal*2
Speed(H-M-L) r/min 1130/950/820/780
Fan motor output/ input power W 85/111
Air-ow(H-M-L) m³/h 1440/1140/900/800
External static pressure Pa 25/37//50/70/90/100/110/120/130/150
Heat
exchanger
Type / Diameter mm Inner grooved pipe/φ7.0
Row 3
Total Area 7.668
Dimension
External(L*W*H) mm×mm×mm 957/655/250
Package(L*W*H) mm×mm×mm 1170/860/340
Drainage pipe (Material, I.D./O.D.) mm PVC 25/29
Controller
(O-Optional,S-Standard)
Wired YR-E16(O)/YR-E17
Fresh air hole dimension mm None
Electricity heater kW None
Sound power Noise level
(H-M-L) dB(A) 58
Sound pressure Noise level (H-M-L) dB(A) 42/38/35
Pipe
Liquid Pipe(mm) 9.52
Gas Pipe(mm) 15.88
Connecting method Flared
Weight (Net / Shipping) kg / kg 31.2/36.8
Norminal condition: indoor temperature (Cooling): 27°C DB/19°C WB, indoor temperature (Heating): 20°C DB
Outdoor temperature (Cooling): 35°C DB/24°C WB, outdoor temperature (Heating): 7°C DB/6°C WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated
sound intensity meter.