EasyManua.ls Logo

Haier AD35S2SM3FA - Page 117

Haier AD35S2SM3FA
257 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
114
Item Model
4U85S2SR2FA
Piping
Refrigerant
Type/Charge kg R32 / 2.2
GWP 675
No Need to Recharge m 40
Recharge g/m 20
Pipe
Liquid mm 4/Φ6.35
Gas mm 3*Φ9.52+1*Φ12.7
Connecting Method - Flared
Between
I.D&O.D
Drop Between IU & OU m ≤7.5
Piping Length Between IU & OU m ≤10
Total Liquid Piping Length m ≤40
Drop Between Indoor Units m ≤1
Max. Drop Between IU &OU m 15
Max. Drop Between Indoor Units m 7.5
Max. Piping Length Between IU & OU m 25
Max. Cable Length Between IU & OU m 30
Max.Total Length m 70
Working Temperature
Cooling °C -10~46
Heating °C -15~24
Tdisignh: -10°C Tbivalent: -7°C TOL: -15°C
Pto: 42W Psb: 16W Pck: 0W Poff: 0W
Cooling
A (Cap/EER) 8652W/3.2
Heating
A (Cap/COP) 6073W/2.78 Tol (Cap/COP) 7020W/2.64
B (Cap/EER) 5746W/5.73 B (Cap/COP) 3702W/3.87 Tb (Cap/COP) 6073W/2.78
C (Cap/EER) 3449W/8.27 C (Cap/COP) 2299W/4.67 Cd (Cooling) 0.25
D (Cap/EER) 3834W/11.55 D (Cap/COP) 2563W/5.92 Cd (Heating) 0.25
Max. Cooling Condition
Indoor
Temperature:
32°C/23°C
Max. Heating Condition
Indoor Temperature: 27°C/-°C
Outdoor
Temperature:
46°C/-°C
Outdoor Temperature: 24°C/18°C
kWh/Annum 372 kWh/Annum-Average 2126 kWh/Annum-Warm 1023
1. The Above performance data are from the combination of 4U85S2SR2FA+3*AS25S2SF2FA+1*AS35S2SF2FA.
2. Large drop and long piping installation will obviously reduce the total capacity.