115
Item Model
5U105S2SS2FA
Function
——
Cooling Heating
Rating capacity
W
10000 10500
Cooling Pdesign
W
10000
Heating Pdesign(-10°C)
W
8000
Rated power input (indoor + outdoor)
W
3400 2800
Rated current input (indoor + outdoor)
A
15.5 12.2
EER / COP
W/W
3.0 3.8
SEER / SCOP
W/W
7.0 4.0
Minimum capacity
W
3200 4400
Minimum power input
W
550 550
Maximum capacity
W
11000 11500
Maximum power input (indoor + outdoor)
W
4100 3400
Power source
——
1PH, 220-240V~, 50/60Hz
Max.Running current (indoor + outdoor)
A / A
17.8 14.6
Power facor(under rating power input)
——
99% 99%
Starting current
A
5
Fuse size (recommended size)
A
25
Outdoor unit
Compressor
Model / Manufacture —— TVB220FAEMC-L/ MELCOM
Oil charge and type —— 870CC/ FW68S
Type —— Twin Rotary (DC inverter)
Number —— 1
Fan
Type × Number —— Axial × 1
Speed r/min High 800
Motor output/input power W 90/130
Air-ows (H/M/L) m³/h About 4200
Heat
exchanger
Type / Diameter mm TP2M / 7.0
Row —— 2
Face area m² About 0.65
"Dimension
(WxDxH)"
External mm 920/372/760
Package mm 1036/478/820
Refrigerant control method —— PMVs
Defrosting method —— Automatic by reversible cycle
Crankcase heater power W NONE
Noise level
Sound power level dB(A) 71
Sound pressure level dB(A) 55
Weight Net / Shipping
kg /
kg
66/71