EasyManua.ls Logo

Haier AD35S2SM3FA - Page 67

Haier AD35S2SM3FA
257 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
64
Item Model AD71S2SM3FA/1UH071N1ERG
Function Cooling Heating
Capacity kW 7.1(2.0~9.0) 8(2.0~10.0)
Sensible heat ratio 0.72 /
Total power input kW 2.03(0.4~4.0) 2.0(0.4~4.0)
Max. power input W 4000 4000
EER or COP W/W 3.5(B) 4(C)
Dehumidifying capacity 10
-3
×m
3
/h 2.4
Power cable /
Power source N, V, Hz 1PH, 220-240V~, 50/60Hz
Running/Max. Running current A/A
8.8(2.0-17.5)/17.5 8.0(2.0-17.5)/17.5
Start current A 0.52
Circuit breaker A 5 5
Indoor unit
Unit model (color) AD71S2SM3FA
Fan
Type×Number CENTRIFUGALX2
Speed (H-M-L) r/min 950/850/750/700 (37Pa)
Fan motor output/ input power kW 0.228
Air-ow (H-M-L) kW 0.160
External static pressure m
3
/h
1440/1260/1100/900(25/37(default)/
50/70/90/100/110/120/130/150Pa)
Heat
exchanger
Type/Diameter mm Inner grooved pipe/φ7.0
Total area m
2
/
Dimension
External (L×W×H) mm×mm×mm 1100*700*248
Package (L×W×H) mm×mm×mm 1290/840/320
Drainage pipe (material, I.D./O.D.) mm PVC 21/25
Controller (O-Optional, S-Standard)
Wired YR-E17(S)
Infrared YRHBS(O)
Fresh air hole dimension mm 123
Electricity heater kW 0
Sound power Noise level (H-M-L) dB (A) 58
Sound pressure Noise level (H-M-L) dB (A) 42/38/35
Weight (Net / Shipping) kg / kg 31/37
Piping
Refrigerant
Type / Charge
g
R410A/2500
Recharge quantity
g/m
45
Pipe
Liquid
mm
9.52
Gas
mm
15.88
Between I.D
&O.D
MAX.Drop
m
30
MAX.Piping length
m
50
Norminal condition:
Indoor temperature (cooling): 27°C DB/19°C WB, indoor temperature (heating): 20°C DB
Outdoor temperature (cooling): 35°C DB/24°C WB, outdoor temperature (heating): 7°C DB/6°C WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity
meter. It is a sound pressure noise level.

Other manuals for Haier AD35S2SM3FA

Related product manuals