65
Item Model AD90S2SM3FA/1UH090N1ERG
Function Cooling Heating
Capacity kW 8.5(2.5~10) 9.5(2.5~11)
Sensible heat ratio 0.72 /
Total power input kW 2.50(0.5~4.4) 2.50(0.5~4.4)
Max. power input W 4400 4400
EER or COP W/W 3.4(B) 3.8(C)
Dehumidifying capacity 10
-3
×m
3
/h 2.5
Power cable /
Power source N, V, Hz 1PH, 220-240V~, 50/60Hz
Running/Max. Running current A/A
11.1(2.3-19.2)/19.2 11.1(2.3-19.2)/19.2
Start current A 0.56
Circuit breaker A 5 5
Indoor unit
Unit model (color) AD90S2SM3FA
Fan
Type×Number CENTRIFUGALX2
Speed (H-M-L) r/min 1050/980/920/860(37Pa)
Fan motor output/ input power kW 0.260
Air-ow (H-M-L) kW 0.180
External static pressure m³/h
1440/1260/1100/900(25/37(default)/
50/70/90/100/110/120/130/150Pa)
Heat
exchanger
Type/Diameter mm Inner grooved pipe/φ7.0
Total area m
2
/
Dimension
External (L×W×H) mm×mm×mm 1100*700*248
Package (L×W×H) mm×mm×mm 1290/840/320
Drainage pipe (material, I.D./O.D.) mm PVC 21/25
Controller (O-Optional, S-Standard)
Wired YR-E17(S)
Infrared YRHBS(O)
Fresh air hole dimension mm 123
Electricity heater kW 0
Sound power noise level (H-M-L) dB (A) 60
Sound pressure noise level (H-M-L) dB (A) 44/40/37
Weight (Net / Shipping) kg / kg 38/45
Piping
Refrigerant
Type / Charge
g
R410A/2500
Recharge quantity
g/m
45
Pipe
Liquid
mm
9.52
Gas
mm
15.88
Between I.D
&O.D
MAX.Drop
m
30
MAX.Piping length
m
50
Norminal condition:
Indoor temperature (cooling): 27°C DB/19°C WB, indoor temperature (heating): 20°C DB
Outdoor temperature (cooling): 35°C DB/24°C WB, outdoor temperature (heating): 7°C DB/6°C WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity
meter. It is a sound pressure noise level.