The Machineis Adaptive in Following Situation
Safety Precautions
1. Applicable ambient temperature range:
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualied
person.
3. If the fuse on the indoor PC board is broken please change it with the type of T5.0/250V (For series
AD35/50/71S2SM3/4FA)
4. The wiring method should be in line with the local wiring standard.
5. The power cable should be:
H05RN-F 3G 4.0mm
2
;
The connecting cable should be:
H05RN-F 4G 2.0mm
2
All the cables shall have got the European authentication certicate. During installation, when the connecting cables
break off, it must be assured that the grouding wire is the last one to be broken off.
6. The power cable and connect cable should be self-provided.
7. The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be
no less than 3mm.
8. The indoor unit installation height is at least 2.5m.
9. A leakage breaker must be installed.
10.For AD35S2SM3FA/AD35S2SM4FA/AD50S2SM3FA/AD50S2SM4FA/AD71S2SM3FA, we can get the 10
different ESP through adjust wired controller YR-E17, please refer below:
Stactic Pressure
Grade
1 2 3 4 5 6 7 8 9 10
Stactic Pressure 25Pa 37Pa 50Pa 70Pa 90Pa 100Pa 110Pa 120Pa 130Pa 150Pa
Adjsutment metchod bywired controller YR-E17: In the state of ON and non screen saving state, press Fan+Set
keys for 5s to enter static pressure grade adjustmentstate with static pressure icon ashing and current
staticpressure grade statically displaying. Press key↑↓ to changestatic pressure grade, then press Set key to
conrm.
Details please refer to wired controller operation & installation manual.
Adjsutment metchod by Infrared remote controller+Infrared receiver RE-02: Step a: set the Infrared remote
controller at condition: FAN mode, fan speed high Step b: then aim the remote controller at the infrared remote
receiver RE-02, press HEALTH button 4+N times (1≤N≤10, integer) within 12 seconds, then the receiver will beep
N+1 times, the static pressure level N is been set successfully.
Note: For Infrared remote controller YR-HBS01, need press ON/OFF button make the controller’s at OFF status
rst, then open the button cover press FRESH button will enter FAN mode interface.
Cooling
Indoor Temperature
Max. DB/WB
Min. DB/WB
32/23°C
18/14°C
Outdoor Temperature
Max. DB/WB
Min. DB/WB
46/26°C
10/6°C
Heating
Indoor Temperature
Max. DB/WB
Min. DB/WB
27°C
15°C
Outdoor Temperature
Max. DB/WB
Min. DB/WB
24/18°C
15°C
AD35S2SM3FA AD50S2SM3FA AD71S2SM3FA