92
Air outlet frame
Electrical components Case
Drain pan Evaporator
Drain opening
AD35S2SM3FA AD35S2SM4FA
AD50S2SM3FA AD50S2SM4FA
AD71S2SM3FA AD71S2SM4FA
Installation Manual For Wire Controller
5. Wiring connections of wire controller:
6. Communication wiring:
There are three methods to connection wire controller and the indoor units:
A. One wired controller can control max. up to 16 sets of indoor units, and 3 pieces of polar wire must connect the
wire controller and the master unit (the indoor unit connected with wire controller directly), the others connect with
the master unit through 2 pieces of polar wire.
B. One wire controller controls one indoor unit, and the indoor unit connects with the wire controller through 3
pieces of polar wire.
C. Two wired controllers control one indoor unit. The wire controller connected with indoor unit is called master
one, the other is called slave one. Master wire controller and indoor unit; master and slave wire controllers are all
connected through 3 pieces of polar wire.
The wire controller is equipped with special communication wiring in the accessories. 3-core terminal (1-white
2-yellow 3-red) is connected with the terminal A, B, C of wire controller respectively.
The communication wiring is 5 meter long; If the actual length is more than it, please distribute wiring according to
below table:
One side of the shielded sheet of communication wire must be earthed.
Communication Wiring Length (m) Dimensions of Wiring
< 100 0.3mm
2
x3-Core Shielded Wire
≥100 and <200 0.5mm
2
x3-Core Shielded Wire
≥200 and <300 0.75mm
2
x3-Core Shielded Wire
≥300 and <400 1.25mm
2
x3-Core Shielded Wire
≥400 and <600 2mm
2
x3-Core Shielded Wire