201
BM1 (1-ON, 0-OFF)
Capacity (SW1-1→SW1-3)
Room
card
SW1-4
Running
mode
SW1-5
Unit Type
Description
SW1-1 SW1-2 SW1-3 SW1-6 SW1-7 SW1-8
ON OFF ON --- --- --- --- --- ADH105M1ERG
OFF ON ON --- --- --- --- --- ADH125M1ERG AD125S2SM3FA
ON ON ON --- --- --- --- --- ADH140M1ERG AD140S2SM3FA
--- --- --- ON --- --- --- --- Room card valid
--- --- --- OFF --- --- --- --- Room card invalid (default)
--- --- --- --- ON --- --- --- Cool only
--- --- --- --- OFF --- --- --- Cool and heat (default)
--- --- --- --- OFF ON OFF Medium ESP DUCT
--- --- --- --- ON ON OFF High ESP DUCT
AD125S2SM3FA AD140S2SM3FA
PCB code 0151800106E
SW3-1 SW3-2 SW3-3 SW3-4
Indoor unit Address
(Indoor unit address for one wired
controller control more than one unit)
OFF OFF OFF OFF 0 (master)
OFF OFF OFF ON 1(slave)
OFF OFF ON OFF 2(slave)
OFF OFF ON ON 3(slave)
OFF ON OFF OFF 4(slave)
OFF ON OFF ON 5(slave)
OFF ON ON OFF 6(slave)
OFF ON ON ON 7(slave)
ON OFF OFF OFF 8(slave)
ON OFF OFF ON 9(slave)
ON OFF ON OFF 10(slave)
ON OFF ON ON 11(slave)
ON ON OFF OFF 12(slave)
ON ON OFF ON 13(slave)
ON ON ON OFF 14(slave)
ON ON ON ON 15(slave)
Wired controller communication address