EasyManua.ls Logo

Haier AD50S2SM1FA - Specification

Haier AD50S2SM1FA
257 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36
2. Specication
Item Model AD25S2SS1FA
Function —— Cooling Heating
Capacity W 2500 3000
Sensible heat ratio W 0.71 /
Dehumidifying capacity 10-³xm³/h 1.0
Indoor unit
Power supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*2
Speed(H-M-L) r/min 850/750/650/600
Fan motor output/input power W 11/15
Air-ows (H-M-L) m³/h 530/460/390/330
External static pressure pa 0/10/20/30
Heat exchanger
Type / Diameter mm Inner grooved pipe/φ7.0
Row —— 2
Total area 0.11
Temp.scope °C 2.0-7.0
Dimension
(LxWxH)
External mmxmmxmm 850x420x185
Package mmxmmxmm 1045x540x270
Drainage pipe (Material,I.D/O.D) mm PVC 27/31
control type(Remote/Wired) Wired YR-E17(O) or Remote YR-HBS01(O)
Fresh air hole dimension mm None
Electricity heater kW None
Noise level
(H-M-L)
Sound power level dB(A) 51
Sound pressure level dB(A) 33/30/26/23
Weight(Net/Shipping) kg/kg 16/21
panel
(optional)
Panel model(Color) P1B-890IA/D
Dimension
External(L*W*H) mmxmmxmm
890/190/100
(Outlet panel)/
890/290.5/32.4
(Inlet panel)
Package(L*W*H) mmxmmxmm 938/335/220
Weight(Net/Shipping) kg/kg 4/5
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ6.35(1/4)
Gas mm Φ9.52(3/8)
Connecting method Flared
Norminal condition: indoor temperature (cooling): 27°CDB/19°CWB, indoor temperature (heating): 20°CDB
Outdoor temperature(cooling): 35°CDB/24°CWB, outdoor temperature(heating): 7°CDB/6°CWB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound
intensity meter.

Related product manuals