Quit condition of oil return:
1 minute later after oil return is over
TdTcm30
OR OR TsTc30
Tc35
Max. 10 minutes
Oil return procedure in heating mode:
Quit condition of oil return
Max. 9 minutesE
OR OR TdTcm20 for 30s5 minutes later, begin to count
T s Tc15 for 30 S5 minutes later, begin to count
Running for min. 5 minutesE
Send oil return signal oil return beginning oil return over
Inverter compressor indicated FQY 60s oil return frequency 120s
Soft startup
0HZ
0HZ
5s
outdoor motor auto auto
autoTC control
4-way valve ON
OFF
15s
450pulse 450 pulse
300pulse E
PMV auto open angel auto open angle
all indoor motor ON
OFF anti-freeze startup
Quit condition of oil return:
Oil return procedure in heating mode:
Quit condition of oil return
OR
OR
OR
OR
Max.9 minutes (E)
Max.10 minutes
Running for min.5 (E)
1 minutes later after oil return is over
Td-Tcm
20°C for 30s (5 minutes later, begin to count)
Td-Tcm
30°C
Ts- Tc
15°C for 30s (5 minutes later, begin to count)
Ts- Tc
30°C
Ts- Tc
-35°C
&
&