230
3U55S2SR2FA   3U70S2SR2FA   4U75S2SR2FA   4U85S2SR2FA   5U105S2SS2FA
Code
Diagnosis
Code
Diagnosis
IPM overcurrent or short circuit 
20
23
18
Module  operated overload
Module  low or high  voltage
Communication failure between Module and ECU
Module current detect circuit malfunction
MCU reset
Discharging temperature overheating.Lack of refrigerant,
ambient temperature too high or PMVs blocked.
17 4-way valve switching failure 
9
10
11
12
13
15
1
2
4
5
6
Malfunction of defrosting temp. sensor  
Malfunction of compressor suction temp. sensor  
Malfunction of condensing temp. sensor
Malfunction of ambient temp. sensor
Malfunction of compressor discharge temp. sensor  
System low pressure switch off  
System low pressure protection.Refrigerant shortage,
Low defrosting temp.,Faulty of model code. or malfunction of fan motor
 
Faulty of outdoor unit EEPROM  
Communication failure between indoor&outdoor unit  
Compressor start failure
Module input overcurrent  
Malfunction of the DC fan motor
Diagnosis using the Numeral Light Indicator
System high pressure switch off  
8
System high pressure protection.Refrigerant overabundance,
High condensing temp. or malfunction of fan motor.
 
OFF OFF OFF
OFF
ON OFF OFF OFF
OFF ON
OFF
OFF
OFF OFF ON OFF
 1  2  3  4
   Definition
State when out of factory 
Compulsive Heating:
Frequency 50HZ; PMV 200 pulse;
Class 5 of outdoor fan motor.
Rated Operating
   Definition of SW1 on Malfunction Display 
Module  thermal overload
24
25
26
27
28
Loss of synchronism detection
Indoor thermal overload
42
43
44
45
38
ON
OFFOFF
OFF
Time Defrost Valid
ON
ONONON
Detection for Wrong Wiring
0150526300
Compulsive Cooling:
Frequency 60HZ; PMV 200 pulse;
Class 7 of outdoor fan motor.
Malfunction of liquid pipe temp. sensor for indoor unit A 
29
30
31
32
33
34
35
36
40
Malfunction of liquid pipe temp. sensor for indoor unit B  
Malfunction of liquid pipe temp. sensor for indoor unit C  
Malfunction of liquid pipe temp. sensor for indoor unit D  
Malfunction of   gas  pipe temp. sensor for indoor unit A 
Malfunction of   gas  pipe temp. sensor for indoor unit B 
Malfunction of   gas  pipe temp. sensor for indoor unit C 
Malfunction of   gas  pipe temp. sensor for indoor unit D
Malfunction of   gas  pipe temp. sensor for indoor unit E 
Notes:
1.When using this product,you need not to  set the address.
   But the L/N wires between  indoor & outdoor units must be
   corresponded,or there will be communication failure.
2.Quiet Operation Setting.Set the DIP ”8” to ON position of
   SW5,the system will run  with lower noise,but the max 
   capacity will also reduce slightly.
3.Do NOT change the settings of other switchs,wrong settings
   can make the system damage or other malfunctions.
4.For some malfunctions, this system can
   make back up running.
  * ECU:Electronic  Control  Unit
  * MCU:Micro Control Unit
  * PMV:Pulse Modulated Valve
  Momentary power failure detection
Malfunction of liquid pipe temp. sensor for indoor unit E  
PRODUCT  DIAGNOSIS  PROCEDURE
39